Air Handling Unit, Ducts and Fan Coils Sanitized at a Medical Centre
Surface swabs taken before and after the work showed over 99.9% fewer microorganisms in the treated areas.
A medical centre in Bassano del Grappa, Italy, asked AirBio to clean and sanitize its whole air system: the air handling unit, the supply ducts and the room units. The same sequence is what we follow on a superyacht HVAC system.
The job in four lines
Site
Centro IMED, a medical centre in Bassano del Grappa (Italy). Work carried out in January 2021.
Systems
Air handling unit, supply ducts, split units and fan coils.
Method
Ozone saturation, mechanical brushing with continuous extraction, detergent and rinse.
Result
Microorganisms on the surfaces down by over 99.9%, measured with swabs.
Why the clinic asked for it
The goal was cleaner indoor air, less microbial contamination and a system that keeps working efficiently.
This project was carried out ashore by AirBio, the company AirBio Marine belongs to. The same technicians, equipment, sanitizing method and end-of-job report are used on board yachts and superyachts.
In a medical centre the air reaches waiting rooms, offices and diagnostic rooms all day. Dust and biofilm build up quietly inside the air handling unit and the ducts, where nobody looks, until they are sampled.
Before starting, the team took surface swabs in two areas: the front office and the plenum of the radiology department. These became the baseline for the final check.


Air handling unit first, then ducts and room units
Air handling unit. The unit was first saturated with ozone. Panels were opened and the panel filters removed. Filtration, humidification and fan sections were sprayed with detergent and rinsed with a pressure washer. The humidifier tank, droplet separator, exchange surfaces and nozzles were treated with a specific product.
Ducts. Access openings were closed with proper inspection doors. Inside, the ducts were brushed mechanically while a continuous extraction system collected the dust.
Split units and fan coils. Each unit was opened, the filters removed, and the inside cleaned with detergent and rinsed.
Swabs before and after
| Sampling point | Parameter | Before | After | Reduction |
|---|---|---|---|---|
| Front office | Microorganisms (per 100 cm²) | over 300,000 | under 40 | over 99.98% |
| Front office | Yeasts and moulds (per 100 cm²) | over 1,500,000 | under 50 | over 99.99% |
| Radiology plenum | Microorganisms (per 100 cm²) | 3,200 | 70 | 97.8% |
| Radiology plenum | Yeasts and moulds (per 100 cm²) | 350 | under 50 | over 85.7% |
Values as published in the AirBio case study. Advice left to the client: check the air handling unit every year and clean the ducts at least every two years.


The same sequence on a superyacht HVAC system
- On a superyacht the air handling units sit in technical spaces and the ducts run behind joinery: we open only what is needed and protect the interiors.
- We take swabs before we start, so the captain gets a baseline and a measured result, not just photos.
- Ozone saturation, mechanical brushing with extraction and a final rinse follow the same order as in this clinic.
- The end-of-job report lists the systems, the method, the products with their data sheets, photos and the next check date.
Questions about this case
Was this job done on a yacht?
No. It was carried out ashore by AirBio at a medical centre. We publish it because the systems, the method, the team and the report are the same ones we use on yachts and superyachts.
What do the swab values mean?
They count microorganisms and moulds found on a 100 cm² surface inside the system. Comparing before and after shows how much of the contamination was removed.
Can you take swabs on my yacht too?
Yes. Pre- and post-work swabs can be added to any HVAC job, so the result is measured and written in the report.
How often should the ducts be cleaned?
The advice given here was to check the air handling unit every year and clean the ducts at least every two years. On a yacht we adjust this to how many hours the system runs and to the charter season.
Where these figures come from
All data on this page come from the original AirBio case study, published on airbio.it.
Pulizia e sanificazione delle condotte aerauliche al Centro IMED
Full description of the job, photos and swab results.
The services behind this job

Industrial plant: supply ducts and insulation
29,000 to under 10 microorganisms per 100 cm².

Diagnostic centre: fan coils and splits
Mould on panels and deposits in the condensate trays.

Professional kitchen: hoods, ducts and fan
A blocked extraction system brought back to work.

Motor yacht: water system and fan coils
Water and air treated during the same yard stop.
Water and air in the same stop?
Tell us the yacht, what the crew has noticed and where she is now: a technician calls you back within 24 hours and plans both sides around your programme.
Tell us about the yacht
Yacht length, marina, systems and what you have noticed on board. A technician reads the message and calls you back to plan the survey.
"*" indicates required fields
Where we work
Italian Riviera and Tuscany marinas and yards — Viareggio, La Spezia, Portofino, Genoa, Sanremo, Livorno, Argentario — and other Mediterranean ports on request.
Documented work
Every job ends with a technical report and photos for the yacht's records.